General specifications |
Signal type |
Digital Output |
Functional safety related parameters |
Safety Integrity Level (SIL) |
SIL 2 |
Supply |
Connection |
Power Rail or terminals 14+, 15- |
Rated voltage |
20 ... 30 V DC |
Power consumption |
max. 3.3 W at 45 mA output current |
Input |
Connection side |
control side |
Connection |
terminals 7, 8, 9 |
Input current |
approx. 3 mA at 24 V DC |
Signal level |
1-signal: 16 ... 30 V DC
0-signal: 0 ... 5 V DC |
Output |
Connection side |
field side |
Connection |
channel 1: terminals 1+, 2-, 3
channel 2: terminals 4+, 5-, 6- |
Internal resistor |
272 Ω |
Current |
≤ 45 mA |
Voltage |
≥ 11.7 V |
Open loop voltage |
min. 24 V |
Output signal |
These values are valid for the rated operating voltages from 20 ... 30 V DC. |
Energized/De-energized delay |
≤ 20 ms / ≤ 20 ms |
Line fault detection |
signal at short-circuit RB < 50 Ω, lead breakage RB > 10 kΩ , test current < 650 µA |